Simatic Wincc Siemens Simatic Wincc

Do you want an email whenever new security vulnerabilities are reported in Siemens Simatic Wincc?

By the Year

In 2021 there have been 1 vulnerability in Siemens Simatic Wincc with an average score of 5.5 out of ten. Last year Simatic Wincc had 2 security vulnerabilities published. If vulnerabilities keep coming in at the current rate, it appears that number of security vulnerabilities in Simatic Wincc in 2021 could surpass last years number. Last year, the average CVE base score was greater by 1.60

Year Vulnerabilities Average Score
2021 1 5.50
2020 2 7.10
2019 5 8.02
2018 1 7.50

It may take a day or so for new Simatic Wincc vulnerabilities to show up. Additionally vulnerabilities may be tagged under a different product or component name.

Latest Siemens Simatic Wincc Security Vulnerabilities

A vulnerability has been identified in SIMATIC PCS 7 (All versions), SIMATIC WinCC (All versions < V7.5 SP2)

CVE-2020-10048 5.5 - Medium - February 09, 2021

A vulnerability has been identified in SIMATIC PCS 7 (All versions), SIMATIC WinCC (All versions < V7.5 SP2). Due to an insecure password verification process, an attacker could bypass the password protection set on protected files, thus being granted access to the protected content, circumventing authentication.

authentification

A vulnerability has been identified in SIMATIC Automation Tool (All versions)

CVE-2020-7580 6.7 - Medium - June 10, 2020

A vulnerability has been identified in SIMATIC Automation Tool (All versions), SIMATIC NET PC software (All versions V16 < V16 Upd3), SIMATIC PCS neo (All versions < V3.0 SP1), SIMATIC ProSave (All versions), SIMATIC S7-1500 Software Controller (All versions < V21.8), SIMATIC STEP 7 (All versions < V5.6 SP2 HF3), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2 Update 4), SIMATIC STEP 7 (TIA Portal) V14 (All versions < V14 SP1 Update 10), SIMATIC STEP 7 (TIA Portal) V15 (All versions < V15.1 Update 5), SIMATIC STEP 7 (TIA Portal) V16 (All versions < V16 Update 2), SIMATIC WinCC OA V3.16 (All versions < P018), SIMATIC WinCC OA V3.17 (All versions < P003), SIMATIC WinCC Runtime Advanced (All versions < V16 Update 2), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2 Update 4), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1 Update 10), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Update 5), SIMATIC WinCC Runtime Professional V16 (All versions < V16 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 14), SIMATIC WinCC V7.5 (All versions < V7.5 SP1 Update 3), SINAMICS STARTER (All Versions < V5.4 HF2), SINAMICS Startdrive (All Versions < V16 Update 3), SINEC NMS (All versions), SINEMA Server (All versions), SINUMERIK ONE virtual (All Versions < V6.14), SINUMERIK Operate (All Versions < V6.14). A component within the affected application regularly calls a helper binary with SYSTEM privileges while the call path is not quoted.

Unquoted Search Path or Element

A vulnerability has been identified in OpenPCS 7 V8.1 (All versions)

CVE-2019-19282 7.5 - High - March 10, 2020

A vulnerability has been identified in OpenPCS 7 V8.1 (All versions), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd3), SIMATIC BATCH V8.1 (All versions), SIMATIC BATCH V8.2 (All versions), SIMATIC BATCH V9.0 (All versions < V9.0 SP1 Upd5), SIMATIC NET PC Software (All versions < V16 Update 1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions < V9.0 Upd4), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Update 10), SIMATIC WinCC (TIA Portal) V15.1 (All versions < V15.1 Update 5), SIMATIC WinCC (TIA Portal) V16 (All versions < V16 Update 1), SIMATIC WinCC V7.3 (All versions), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 14), SIMATIC WinCC V7.5 (All versions < V7.5 SP1 Update 1). Through specially crafted messages, when encrypted communication is enabled, an attacker with network access could use the vulnerability to compromise the availability of the system by causing a Denial-of-Service condition. Successful exploitation requires no system privileges and no user interaction.

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions)

CVE-2019-10935 7.2 - High - July 11, 2019

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd 11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC Professional (TIA Portal V13) (All versions), SIMATIC WinCC Professional (TIA Portal V14) (All versions < V14 SP1 Upd 9), SIMATIC WinCC Professional (TIA Portal V15) (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). The SIMATIC WinCC DataMonitor web application of the affected products allows to upload arbitrary ASPX code. The security vulnerability could be exploited by an authenticated attacker with network access to the WinCC DataMonitor application. No user interaction is required to exploit this vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the affected device. At the stage of publishing this security advisory no public exploitation is known.

Unrestricted File Upload

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions)

CVE-2019-10916 8.8 - High - May 14, 2019

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with access to the project file could run arbitrary system commands with the privileges of the local database server. The vulnerability could be exploited by an attacker with access to the project file. The vulnerability does impact the confidentiality, integrity, and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Improper Input Validation

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions)

CVE-2019-10917 5.5 - Medium - May 14, 2019

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An attacker with local access to the project file could cause a Denial-of-Service condition on the affected product while the project file is loaded. Successful exploitation requires access to the project file. An attacker could use the vulnerability to compromise availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Improper Input Validation

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions)

CVE-2019-10918 8.8 - High - May 14, 2019

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An authenticatd attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. The vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires authentication with a low-privileged user account and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Improper Input Validation

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions)

CVE-2019-10922 9.8 - Critical - May 14, 2019

A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 and newer (All versions), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 and newer (All versions). An attacker with network access to affected installations, which are configured without "Encrypted Communication", can execute arbitrary code. The security vulnerability could be exploited by an unauthenticated attacker with network access to the affected installation. No user interaction is required to exploit this security vulnerability. The vulnerability impacts confidentiality, integrity, and availability of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

Authorization

A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions)

CVE-2018-4832 7.5 - High - April 24, 2018

A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versions), OpenPCS 7 V8.1 (All versions < V8.1 Upd5), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd1), SIMATIC BATCH V7.1 and earlier (All versions), SIMATIC BATCH V8.0 (All versions < V8.0 SP1 Upd21), SIMATIC BATCH V8.1 (All versions < V8.1 SP1 Upd16), SIMATIC BATCH V8.2 (All versions < V8.2 Upd10), SIMATIC BATCH V9.0 (All versions < V9.0 SP1), SIMATIC NET PC-Software (All versions < 15 SP1), SIMATIC PCS 7 V7.1 and earlier (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP1), SIMATIC Route Control V7.1 and earlier (All versions), SIMATIC Route Control V8.0 (All versions), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions < V9.0 Upd1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2 Upd2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1 Upd5), SIMATIC WinCC V7.2 and earlier (All versions < WinCC 7.2 Upd 15), SIMATIC WinCC V7.3 (All versions < WinCC 7.3 Upd 16), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 4), SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.

Improper Input Validation

An Improper Input Validation issue was discovered in Siemens SIMATIC PCS 7 V8.1 prior to V8.1 SP1 with WinCC V7.3 Upd 13

CVE-2017-14023 4.9 - Medium - November 06, 2017

An Improper Input Validation issue was discovered in Siemens SIMATIC PCS 7 V8.1 prior to V8.1 SP1 with WinCC V7.3 Upd 13, and V8.2 all versions. The improper input validation vulnerability has been identified, which may allow an authenticated remote attacker who is a member of the administrators group to crash services by sending specially crafted messages to the DCOM interface.

Improper Input Validation

Stay on top of Security Vulnerabilities

Want an email whenever new vulnerabilities are published for Siemens Simatic Wincc or by Siemens? Click the Watch button to subscribe.

subscribe