In 2025 there have been 0 vulnerabilities in Deltaww Infrasuite Device Master. Infrasuite Device Master did not have any published security vulnerabilities last year.
Year | Vulnerabilities | Average Score |
---|---|---|
2025 | 0 | 0.00 |
2024 | 0 | 0.00 |
2023 | 22 | 8.79 |
2022 | 9 | 9.10 |
2021 | 0 | 0.00 |
2020 | 0 | 0.00 |
2019 | 0 | 0.00 |
2018 | 0 | 0.00 |
It may take a day or so for new Infrasuite Device Master vulnerabilities to show up in the stats or in the list of recent security vulnerabilties. Additionally vulnerabilities may be tagged under a different product or component name.
Recent Deltaww Infrasuite Device Master Security Vulnerabilities
In Delta Electronics InfraSuite Device Master v.1.0.7, A vulnerability exists
CVE-2023-47279
7.5 - High
- November 30, 2023
In Delta Electronics InfraSuite Device Master v.1.0.7, A vulnerability exists that allows an unauthenticated attacker to disclose user information through a single UDP packet, obtain plaintext credentials, or perform NTLM relaying.
Directory traversal
In Delta Electronics InfraSuite Device Master v.1.0.7, a vulnerability exists
CVE-2023-46690
8.8 - High
- November 30, 2023
In Delta Electronics InfraSuite Device Master v.1.0.7, a vulnerability exists that allows an attacker to write to any file to any location of the filesystem, which could lead to remote code execution.
Directory traversal
In Delta Electronics InfraSuite Device Master v.1.0.7, a vulnerability exists
CVE-2023-47207
9.8 - Critical
- November 30, 2023
In Delta Electronics InfraSuite Device Master v.1.0.7, a vulnerability exists that allows an unauthenticated attacker to execute code with local administrator privileges.
Marshaling, Unmarshaling
In Delta Electronics InfraSuite Device Master v.1.0.7, a vulnerability exists
CVE-2023-39226
9.8 - Critical
- November 30, 2023
In Delta Electronics InfraSuite Device Master v.1.0.7, a vulnerability exists that allows an unauthenticated attacker to execute arbitrary code through a single UDP packet.
?Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contain improper access controls
CVE-2023-30765
9.8 - Critical
- July 10, 2023
?Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contain improper access controls that could allow an attacker to alter privilege management configurations, resulting in privilege escalation.
Authorization
?An attacker could bypass the latest Delta Electronics InfraSuite Device Master (versions prior to 1.0.7) patch, which could
CVE-2023-34316
7.5 - High
- July 10, 2023
?An attacker could bypass the latest Delta Electronics InfraSuite Device Master (versions prior to 1.0.7) patch, which could allow an attacker to retrieve file contents.
Authorization
?Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contains classes
CVE-2023-34347
9.8 - Critical
- July 10, 2023
?Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contains classes that cannot be deserialized, which could allow an attack to remotely execute arbitrary code.
Marshaling, Unmarshaling
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an unauthenticated attacker could generate a valid token
CVE-2023-1136
7.5 - High
- March 27, 2023
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an unauthenticated attacker could generate a valid token, which would lead to authentication bypass.
AuthZ
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in
CVE-2023-1137
8.8 - High
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which a low-level user could extract files and plaintext credentials of administrator users, resulting in privilege escalation.
Insufficiently Protected Credentials
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain an improper access control vulnerability, which could
CVE-2023-1138
7.5 - High
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain an improper access control vulnerability, which could allow an attacker to retrieve Gateway configuration files to obtain plaintext credentials.
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-gateway service, which could
CVE-2023-1139
8.8 - High
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-gateway service, which could allow deserialization of requests prior to authentication, resulting in remote code execution.
Marshaling, Unmarshaling
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability
CVE-2023-1140
9.8 - Critical
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability that could allow an attacker to achieve unauthenticated remote code execution in the context of an administrator.
Missing Authentication for Critical Function
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a command injection vulnerability
CVE-2023-1141
8.8 - High
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a command injection vulnerability that could allow an attacker to inject arbitrary commands, which could result in remote code execution.
Command Injection
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in
CVE-2023-1133
9.8 - Critical
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow an unauthenticated attacker to remotely execute arbitrary code.
Marshaling, Unmarshaling
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a path traversal vulnerability, which could
CVE-2023-1134
8.8 - High
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a path traversal vulnerability, which could allow an attacker to read local files, disclose plaintext credentials, and escalate privileges.
Directory traversal
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could set incorrect directory permissions
CVE-2023-1135
7.8 - High
- March 27, 2023
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could set incorrect directory permissions, which could result in local privilege escalation.
Incorrect Permission Assignment for Critical Resource
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5
CVE-2023-1142
9.8 - Critical
- March 27, 2023
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use URL decoding to retrieve system files, credentials, and bypass authentication resulting in privilege escalation.
Directory traversal
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use Lua scripts, which could
CVE-2023-1143
8.8 - High
- March 27, 2023
In Delta Electronics InfraSuite Device Master versions prior to 1.0.5, an attacker could use Lua scripts, which could allow an attacker to remotely execute arbitrary code.
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contains an improper access control vulnerability in
CVE-2023-1144
8.8 - High
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contains an improper access control vulnerability in which an attacker can use the Device-Gateway service and bypass authorization, which could result in privilege escalation.
AuthZ
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-DataCollect service, which could
CVE-2023-1145
7.8 - High
- March 27, 2023
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 are affected by a deserialization vulnerability targeting the Device-DataCollect service, which could allow deserialization of requests prior to authentication, resulting in remote code execution.
Marshaling, Unmarshaling
A privilege escalation vulnerability exists in Delta Electronics InfraSuite Device Master 00.00.02a
CVE-2023-0444
8.8 - High
- January 26, 2023
A privilege escalation vulnerability exists in Delta Electronics InfraSuite Device Master 00.00.02a. A default user 'User', which is in the 'Read Only User' group, can view the password of another default user 'Administrator', which is in the 'Administrator' group. This allows any lower privileged user to log in as an administrator.
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-DataCollect service port without proper verification
CVE-2022-41778
8.8 - High
- January 13, 2023
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-DataCollect service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization.
Marshaling, Unmarshaling
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize network packets without proper verification
CVE-2022-41779
9.8 - Critical
- October 31, 2022
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize network packets without proper verification. If the device connects to an attacker-controlled server, the attacker could send maliciously crafted packets that would be deserialized and executed, leading to remote code execution.
Marshaling, Unmarshaling
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior
CVE-2022-41657
9.8 - Critical
- October 31, 2022
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior allow attacker provided data already serialized into memory to be used in file operation application programmable interfaces (APIs). This could create arbitrary files, which could be used in API operations and could ultimately result in remote code execution.
Directory traversal
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lack proper authentication for functions
CVE-2022-41688
7.5 - High
- October 31, 2022
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lack proper authentication for functions that create and modify user groups. An attacker could provide malicious serialized objects that could run these functions without authentication to create a new user and add them to the administrator group.
Missing Authentication for Critical Function
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior mishandle .ZIP archives containing characters used in path traversal
CVE-2022-41772
9.8 - Critical
- October 31, 2022
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior mishandle .ZIP archives containing characters used in path traversal. This path traversal could result in remote code execution.
Directory traversal
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior
CVE-2022-41776
7.5 - High
- October 31, 2022
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to trigger the WriteConfiguration method, which could allow an attacker to provide new values for user configuration files such as UserListInfo.xml. This could lead to the changing of administrative passwords.
Missing Authentication for Critical Function
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-Gateway service port without proper verification
CVE-2022-38142
9.8 - Critical
- October 31, 2022
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-Gateway service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization.
Marshaling, Unmarshaling
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication
CVE-2022-40202
9.8 - Critical
- October 31, 2022
The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution.
Missing Authentication for Critical Function
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior
CVE-2022-41629
9.1 - Critical
- October 31, 2022
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to access the aprunning endpoint, which could allow an attacker to retrieve any file from the RunningConfigs directory. The attacker could then view and modify configuration files such as UserListInfo.xml, which would allow them to see existing administrative passwords.
Missing Authentication for Critical Function
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lacks authentication for a function that changes group privileges
CVE-2022-41644
8.8 - High
- October 31, 2022
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lacks authentication for a function that changes group privileges. An attacker could use this to create a denial-of-service state or escalate their own privileges.
Missing Authentication for Critical Function
Stay on top of Security Vulnerabilities